VERSAPOD DATA CENTRE CABINET THERMAL CAPACITIES

Analysis Overview: This analysis is based on a third-party thermal capacity study of the VersaPOD cabinet using CFD modeling and uses the following parameters:

  • A single 45U VersaPOD was fully populated with 1U/500W servers
  • A perforated floor tile placed in front of the cabinet provides an air output of 13°C (55°F), 600CFM
  • Servers were evenly removed until equipment intake temperatures met manufacturer requirements

ANALYSIS #1: STANDARD VersaPOD CABINET

data centre rack thermal analysis
  • 1000mm (40") VersaPOD cabinet
  • Perforated front and rear doors
  • No fans or vertical blanking panels installed
  • Blanking panels are used in horizontal locations where equipment is not present

(14) servers installed within limits of intake temperatures
(14) x 500W = 7kW capacity

ANALYSIS #2: VersaPOD WITH VERTICAL EXHAUST DUCT & FANS

data centre enclosure thermal analysis
  • 1200mm (48") VersaPOD data centre cabinet
  • Perforated front doors
  • Solid rear doors
  • Vertical exhaust duct
  • 3 fan trays installed in top of cabinet (9 fans total)
  • Blanking panels are used in horizontal locations where equipment is not present

(26) servers installed within limits of intake temperatures
(26) x 500W = 13kW capacity


Need Help?

Ask Siemon

info_uk@siemon.com

+44(0)1932 571 771 (UK)
8am-5:00pm (»Worldwide)


Innovate Magazine
Cisco and Siemon

Cisco Technology Developer Partner


See Siemon in Cisco Marketplace:

Category 7 Cabling?
Cat 7 for the real world Articles and case studies 48 pages
» Learn more

Case Studies - See how Siemon is connecting the world to a higher standard
Find Partners

» Find Siemon Authorized Distributors

» Find Certified Installers & Consultants