Google Translate

Worldwide | United States/Canada

TWISTED-PAIR CABLING INSTALLATION PRACTICES

  • To avoid stretching, pulling tension should not exceed 110N (25 lbƒ) for 4-pair cables.
  • Installed bend radii shall not exceed:
    • 4 times the cable diameter for horizontal UTP cables under no load conditions.
    • 8 times the cable diameter for horizontal ScTP cables.
    • 10 times the cable diameter for multi-pair backbone twisted-pair cables under no load conditions.
  • Horizontal cables should be used with connecting hardware and patch cords (or jumpers) of the same performance category or higher.
  • Avoid cable stress, as caused by:
    • cable twist during pulling or installation
    • tension in suspended cable runs
    • tightly cinched cable ties or staples
    • tight bend radii
  • Important Note: Installed twisted-pair cabling shall be classified by the least performing component in the link.

Share This




Need Help?

Ask Siemon

customer_service@siemon.com

866-548-5814 (US)
8am-6:30pm EST (»Worldwide)


Follow Siemon

hp-rss-icon

10GBASE-T Advancements in Data Centers: Expert Panel Discussion


Cisco and Siemon

Cisco Technology Developer Partner


See Siemon in Cisco Marketplace: