Telecommunications Room
Design:
- Dedicated to telecommunications function.
- Equipment not related to telecommunications shall not be installed, pass through or enter the telecommunications room.
- Multiple closets on the same floor shall be interconnected by a minimum of one 78mm (trade size 3) conduit, or equivalent pathway.
- Minimum floor loading 2.4 kPA (50 lbf/ft2).
Design Considerations:
- Minimum one closet per floor to house telecommunications equipment/cable terminations and associated cross-connect cable and wire.
- Located near the center of the area being served.
- Horizontal pathways shall terminate in the telecommunications room on the same floor as the area served.
- Accommodate seismic zone requirements.
- Two walls should have 21mm (0.75 in.) A-C plywood 2.4m (8 ft.) high.
- Lighting shall be a minimum of 500 lx (50 foot candles) and mounted 2.6m (8.5 ft.) above floor.
- False ceilings shall not be provided.
- Minimum door size 910mm (36 in.) wide and 2000mm (80 in.) high without sill, hinged to open outwards, or slide side-to-side or removable, and fitted with a lock.
- Minimum of two dedicated, non-switched, duplex electrical outlet receptacles or equivalent, each on separate branch circuits.
- Additional convenience duplex outlets placed at 1.8m (6 ft.) intervals around perimeter, 150mm (6 in.) above floor.
- Access to the telecommunications grounding system as specified by ANSI-J-STD-607-A.
- HVAC requirements to maintain temperature the same as adjacent office area. A positive pressure shall be maintained with a minimum of one air change per hour or per code.
|